Product Overview
The open-close current transformer is improved on the basis of the traditional transformer.Made of free opening and closing, it can be quickly installed and disassembled in the state of no power failure and no wire disassembly, and the operation is simple. This series of products has a wide measuring range, rated primary current range: 5~630A, rated secondary current range: 0~5A, current ratio range up to 500:1~ 10,000:1, orderly production process, to ensure its accracy level,reliability and other technical requirements.This product complies with GB/T20840.1.2 standard.
Product Features
▪ Snap structure,good linearity and high sensitivity
▪ High permeability silicon steel with good linearity and high sensitivity
▪ Internal epoxy resin casting, good stability,light weight,eas installation
Scope of Application
It is suitable for rural power grid reconstruction, electrical fire monitoring, fire prevention and leakage system,intelligent power system, power measurement,power quality analysis and electrical equipment signal acquisition,power demand side management of lighting equipment, motor,power device and other equipment,small current grounding system, electromagnetic relay protection,microcomputer protection, intelligent power,environmental protection monitoring, etc.
Performance Index
|
Electrical parameters |
Mechanical parameters |
||
|
Working frequency |
50~2KHz |
Shell |
ABS,Flame retardant grade 94-V0 |
|
Rated input |
5A~2000A |
Skeleton |
PBT |
|
Measuring range |
10%In~130%In |
Iron core |
Ferrite/silicon steel |
|
Rated output |
0.333VIAC) or 0-5A |
Internal structure |
Clasp |
|
Ratio difference |
≤±0.1% |
Construction plan |
Band fixation |
|
Phase difference |
≤±10 points |
Working temperature |
-25℃~+75℃ |
|
Dielectric strength |
2.5KV/1mA/lmin |
Ambient humidity |
≤85% |
|
Insulation resistance |
DC500V/1000MΩ/min |
Connection mode |
PVC tricolor 1.5m twisted pair |
Open-close Type Current Transformer
Outline and installation dimensions
|
Model and specification |
Rated input |
Rated output |
Accuracy class |
Dimensions(mm) |
|||
|
Φ |
A |
B |
C |
||||
|
CTKD10 |
5-75A (5、10、20、50、75) |
0-50mA 0.333V |
0.5、1.0、3.0 |
10mm |
23 |
40 |
27 |
|
CTKD16 |
5-160A (5、10、50、100、160) |
0-5A 0.333V |
16mm |
31 |
50 |
30 |
|
|
CTKD24 |
10-300A (10、50、100、200、250) |
0-5A 0.333V |
23mm |
43 |
73 |
39 |
|
|
CTKD35 |
10-630A (20、100、250、400、600) |
0-5A 0.333V |
35mm |
60 |
89 |
43 |
|
|
CTKD50 |
10-2000A (200、500、1000、1500、2000) |
0-5A 0.333V |
50mm |
81.2 |
119.8 |
58 |
|
Send us an email
Classification :
Keywords : Current Transformer
Keywords : Split-core Current Transformer
Quality begins with details
We are committed to providing outstanding after-sales service, ensuring a seamless support experience. Be it product usage guidance, customization needs, or post-sales inquiries, our professional team is always here to offer fast and attentive service.
Product packaging and shipping site
We Are Always Happy To Help
We are dedicated to providing superior products and services to all our valued customers, in gratitude for their trust and support.
Choose the Product You Need